General Specifications | ||||
DC | ||||
Type | AC power supply models | DC power supply models | ||
Model | CP1E-[][][]S[]D[]-A CP1E-[][][]D[]-A |
CP1E-[][][]S[]D[]-D CP1E-[][][]D[]-D |
||
Enclosure | Mounted in a panel | |||
Dimensions (H × D × W) | E/N/NA[][]-type CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 90mm *1 × 85mm *2 × 66 mm CPU Unit with 14 or 20 I/O points (CP1E-[]14D[]-[]/[]20D[]-[]): 90mm *1 × 85mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-[]30D[]-[]): 90mm *1 × 85mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-[]40D[]-[]): 90mm *1 × 85mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-N60D[]-[]): 90mm *1 × 85mm *2 × 195 mm CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 90mm *1 × 85mm *2 × 130 mm E/N/[][]S(1)-type CPU Unit with 14 or 20 I/O points (CP1E-[]14SD[]-[]/[]20SD[]-[]): 90mm *1 × 79mm *2 × 86 mm CPU Unit with 30 I/O points (CP1E-[]30S(1)D[]-[]): 90mm *1 × 79mm *2 × 130 mm CPU Unit with 40 I/O points (CP1E-[]40S(1)D[]-[]): 90mm *1 × 79mm *2 × 150 mm CPU Unit with 60 I/O points (CP1E-[]60S(1)D[]-[]): 90mm *1 × 79mm *2 × 195 mm |
|||
Weight | CPU Unit with 10 I/O points (CP1E-E10D[]-[]): 300g max. CPU Unit with 14 I/O points (CP1E-[]14(S)D[]-[]): 360g max. CPU Unit with 20 I/O points (CP1E-[]20(S)D[]-[]): 370g max. CPU Unit with 30 I/O points (CP1E-[]30(S[])D[]-[]): 600g max. CPU Unit with 40 I/O points (CP1E-[]40(S[])D[]-[]): 660g max. CPU Unit with 60 I/O points (CP1E-[]60(S[])D[]-[]): 850g max. CPU Unit with 20 I/O points and built-in analog (CP1E-NA20D[]-[]): 680g max. |
|||
Elec-
trical spec- ifica- tions |
Supply voltage | 100 to 240 VAC 50/60 Hz | 24 VDC | |
Operating voltage range |
85 to 264 VAC | 20.4 to 26.4 VDC | ||
Power
consumption |
15 VA/100 VAC max. 25 VA/240 VAC max. (CP1E-E10D[]-A/[]14(S)D[]-A/ []20(S)D[]-A) |
9 W max. (CP1E-E10D[]-D) 13 W max. (CP1E-N14D[]-D/N20D[]-D) |
||
50 VA/100 VAC max. 70 VA/240 VAC max. (CP1E-NA20D[]-A/[]30(S[])D[]-A/ []40(S[])D[]-A/N60(S[])D[]-A) |
20 W max. (CP1E-NA20D[]-D/N30(S[])D[]-D/ N40(S[])D[]-D/N60(S[])D[]-D) *4 |
|||
Inrush current | 120 VAC, 20 A for 8 ms max. for cold start at room temperature 240 VAC, 40 A for 8 ms max. for cold start at room temperature |
24 VDC, 30 A for 20 ms max. for cold start at room temperature |
||
External power supply *3 |
Not provided. (CP1E-E10D[]-A/[]14(S)D[]-A/ []20(S)D[]-A) 24 VDC, 300 mA (CP1E-NA20D[]-A/[]30D[]-A/ []40D[]-A/[]60D[]-A/[]30SDR-A/ []40SDR-A/[]60SDR-A) |
Not provided | ||
Insulation resistance |
20 MΩ min. (at 500 VDC) between the external AC terminals and GR terminals |
Except between DC primary current and DC secondary current |
||
Dielectric strength |
2,300 VAC 50/60Hz for 1 min between AC external and GR terminals Leakage current: 5 mA max. |
Except between DC primary current and DC secondary current |
||
Power OFF detection time |
10 ms min. | 2 ms min. | ||
Appli-
cation envi- ron- ment |
Ambient operating temperature |
0 to 55 °C | ||
Ambient humidity | 10% to 90% | |||
Atmosphere | No corrosive gas. | |||
Ambient storage temperature |
-20 to 75 °C (excluding battery) | |||
Altitude | 2,000 m max. | |||
Pollution degree | 2 or less: Meets IEC 61010-2-201. | |||
Noise resistance | 2 kV on power supply line (Conforms to IEC61000-4-4.) | |||
Overvoltage category |
Category II: Meets IEC 61010-2-201. | |||
EMC Immunity Level |
Zone B | |||
Vibration resistance |
Conforms to JIS 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total) |
|||
Shock resistance | Conforms to JIS 60068-2-27. 147 m/s2, 3 times in X, Y, and Z directions |
|||
Terminal block | Fixed (not removable) | |||
Terminal screw size | M3 | |||
Applicable standards | Conforms to EC Directive | |||
Grounding method | Ground to 100 Ω or less. | |||
* 1 Total of 110 mm with mounting brackets.
|
||||
* 2 Excluding cables. | ||||
* 3 Use the external power supply to power input devices. Do not use it to drive output devices.
|
||||
* 4 This is the rated value for the maximum system configuration. Use the following formula to calculate power
|
||||
consumption for CPU Units with DC power. | ||||
Formula: DC power consumption = (5 V current consumption × 5 V/70% (internal power efficiency) + 24V current
|
||||
consumption) × 1.1 (current fluctuation factor)
|
||||
The above calculation results show that a DC power supply with a greater capacity is required.
|
||||
Performance Specifications | ||||
Item | CP1E-E[][]SD[]-[] CP1E-[][]D[]-[] |
CP1E-N[][]S[]D[]-[] CP1E-N[][]D[]-[] CP1E-NA[][]D[]-[] |
||
Program capacity | 2 K steps (8 Kbytes) including the symbol table, comments, and program indices of the CX-Programmer |
8 K steps (32 Kbytes) including the symbol table, comments, and program indices of the CX-Programmer |
||
Control method | Stored program method | |||
I/O control method | Cyclic scan with immediate refreshing | |||
Program language | Ladder diagram | |||
Instructions | Approximately 200 | |||
Proc-
essing speed |
Overhead processing time | 0.4 ms | ||
Instruction execution times | Basic instructions (LD): 1.19 μs min. Special instructions (MOV): 7.9 μs min. |
|||
Number of CP1W-series Expansion Units connected |
CP1E-E10D[]-[]/[]14(S)D[]-[]/[]20(S)D[]-[]: None CP1E-[]30(S[])D[]-[]/[]40(S[])D[]-[]/[]60(S[])D[]-[]/NA20(S[])D[]-[]: 3 units |
|||
Maximum number of I/O points | CP1E-E10D[]-[]: 10 CP1E-[]14(S)D[]-[]: 14 CP1E-[]20(S)D[]-[]: 20 CP1E-[]30(S[])D[]-[]: 150 (30 built in, 40 × 3 expansion) CP1E-[]40(S[])D[]-[]: 160 (40 built in, 40 × 3 expansion) CP1E-[]60(S[])D[]-[]: 180 (60 built in, 40 × 3 expansion) CP1E-NA20D[]-[]: 140 (20 built in, 40 × 3 expansion) |
|||
Built-in I/O | CP1E-E10D[]-[]: 10 (6 inputs, 4 outputs) CP1E-[]14(S)D[]-[]: 14 (8 inputs, 6 outputs) CP1E-[]20(S)D[]-[]: 20 (12 inputs, 8 outputs) CP1E-[]30(S[])D[]-[]: 30 (18 inputs, 12 outputs) CP1E-[]40(S[])D[]-[]: 40 (24 inputs, 16 outputs) CP1E-[]60(S[])D[]-[]: 60 (36 inputs, 24 outputs) CP1E-NA20D[]-[]: 20 (12 inputs, 8 outputs) |
|||
Built-in
input func- tions |
High-
speed counters |
High-speed counter mode/ maximum frequency |
Incremental Pulse Inputs 10 kHz: 6 counters 5 counters (only for 10 I/O points) Up/Down Inputs 10 kHz: 2 counters Pulse + Direction Inputs 10 kHz: 2 counters Differential Phase Inputs (4x) 5 kHz: 2 counters |
Incremental Pulse Inputs 100 kHz: 2 counters, 10 kHz: 4 counters Up/Down Inputs 100 kHz: 1 counters, 10 kHz: 1 counters Pulse + Direction Inputs 100 kHz: 2 counters Differential Phase Inputs (4x) 50 kHz: 1 counter, 5 kHz: 1 counter |
Counting mode | Linear mode Ring mode |
|||
Count value | 32 bits | |||
Counter reset modes |
Phase Z and software reset (excluding increment pulse input) Software reset |
|||
Control method | Target Matching Range Comparison |
|||
Input interrupts | 6 inputs (4 inputs only for 10 I/O points) Interrupt input pulse width: 50 μs min. |
|||
Quick-response Inputs | 6 inputs (4 inputs only for 10 I/O points) Input pulse width: 50 μs min. |
|||
Normal input |
Input constants | Delays can be set in the PLC Setup (0 to 32 ms, default: 8 ms). Set values: 0, 1, 2, 4, 8, 16, or 32 ms |
||
Built-in
output func- tions |
Pulse
outputs (Models with transistor outputs only) |
Pulse output method and output frequency |
Pulse output function not
included |
Pulse + Direction Mode 1 Hz to 100 kHz: 2 outputs |
Output mode | Continuous mode (for speed control) Independent mode (for position control) |
|||
Number of output pulses |
elative coordinates: 0000 0000 to 7FFF FFFF hex (0 to 2147483647) Absolute coordinates: 8000 0000 to 7FFF FFFF hex (-2147483647 to 2147483647) |
|||
Acceleration/ deceleration curves |
Trapezoidal acceleration and deceleration (Cannot perform S-curve acceleration and deceleration.) |
|||
Changing SVs during instruction execution |
Only target position can be changed. | |||
Origin searches | Included | |||
Pulse
outputs (Models with transistor outputs only) |
Frequency |
PWM output function not
included |
2.0 to 6,553.5 Hz (in increments of 0.1 Hz) with 1 output or 2 Hz to 32,000 Hz (in increments of 1 Hz) with 1 output |
|
Duty factor | 0.0% to 100.0% (in increments of 0.1%) Accuracy: +1%/-0% at 2 Hz to 10,000 Hz and +5%/-0% at 10,000 Hz to 32,000 kHz |
|||
Output mode | Continuous Mode | |||
Built-in analog
|
Analog input |
Analog function not included
|
Setting range: 0 to 6,000 (2 channels only for NA-type) |
|
Analog output | Setting range: 0 to 6,000 (1 channels only for NA-type) |
|||
Analog adjusters | E/N/NA[][]-type: 2 adjusters (Setting range: 0 to 255) E/N[][]S(1)-type: None |
|||
Com-
muni- cations |
B-type Peripheral USB Port | Conforming to USB 2.0 B type connector | ||
Transmission distance |
5 m max. | |||
Built-in RS-232C port |
No built-in RS-232C port
|
Interface: Conforms to EIA RS-232C. | ||
Communications method |
Half duplex | |||
synchronization | Start-stop | |||
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps |
|||
Transmission distance |
15 m max. | |||
Supported protocol |
• Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master |
|||
Built-in RS-485 port |
No built-in RS-485 port
|
N30/40/60S1-type only Interface: Conforms to EIA RS-485. 2-wire sensors No isolation |
||
Communications method |
Half duplex | |||
synchronization | Start-stop | |||
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps |
|||
Transmission distance |
50 m max. | |||
Supported protocol |
• Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master |
|||
Serial Option port |
Option Board cannot be
mounted. |
N30/40/60 and NA20-type only 1 port |
||
Mountable Option Boards |
One RS-232C port: CP1W-CIF01 One RS-422A/485 port (not isolated): CP1W-CIF11 One RS-422A/485 port (isolated): CP1W-CIF12-V1 One Ethernet port: CP1W-CIF41 |
|||
Communications method |
Depends on Option Board. | |||
synchronization | Depends on Option Board. | |||
Baud rate | 1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6, or 115.2 kbps |
|||
Compatible protocols |
• Host Link • 1:N NT Link • No-protocol mode • Serial PLC Links (master, slave) • Modbus-RTU Easy Master |
|||
Number of tasks | 17 • One cyclic execution task • One scheduled interrupt task (always interrupt task 1) • Six input interrupt tasks (interrupt tasks 2 to 7) • Sixteen high-speed counter interrupt tasks (interrupt tasks 1 to 16) |
|||
Maximum subroutine number | 128 | |||
Maximum jump number | 128 | |||
Scheduled interrupt tasks | 1 interrupt task | |||
Clock | Clock function not included. The time of error occurrence displays 01-01-01 01:01:01 Sunday |
Included. Accuracy (monthly deviation): -4.5 min to -0.5 min at ambient temperature of 55°C, -2.0 min to +2.0 min at ambient temperature of 25°C, -2.5 min to +1.5 min at ambient temperature of 0°C |
||
Memory
backup |
Built-in EEPROM | Ladder programs and parameters are automatically saved to built-in EEPROM A section of the Data Memory Area can be saved to the built-in EEPROM. |
||
Battery backup With CP1W-BAT01 Battery (Sold separately) |
Battery cannot be mounted. | CP1W-BAT01 can be used. Maximum battery service life: 5 years Backup Time Guaranteed value (ambient temperature: 55°C): 13,000 hours (approx. 1.5 years) Effective value (ambient temperature: 25°C): 43,000 hours (approx. 5 years) |
||
CIO
Area |
Input Bits | 1,600 bits (100 words): CIO 0.00 to CIO 99.15 (CIO 00 to CIO 99) | ||
Output Bits | 1,600 bits (100 words): CIO 100.00 to CIO 199.15 (CIO 100 to CIO 199) | |||
Serial PLC Link Words | 1,440 bits (90 words): CIO 200.00 to CIO 289.15 (words CIO 200 to CIO 289) | |||
Work Area (W) | 1,600 bits (100 words): W0.00 to W99.15 (W0 to W99) | |||
Holding Area (H) | 800 bits (50 words): H0.00 to H49.15 (H0 to H49) Bits in this area maintain their ON/OFF status when operating mode is changed. |
|||
Auxiliary Area (A) | Read-only: 7,168 bits (448 words) A0 to A447 Read/write: 4,896 bits (306 words) in words A448 to A753 |
|||
Temporary Relay Area (TR) (TR Area) | 16 bits: TR0 to TR15 | |||
Timer Area (T) | 256 timer numbers (T0 to T255 (separate from counters)) | |||
Counter Area (C) | 256 counter numbers (C0 to C255 (separate from timers)) | |||
Data Memory Area (D) | 2 Kwords: D0 to D2047 Of these, 1,500 words can be saved to the backup memory (built-in EEPROM) using settings in the Auxiliary Area. |
8 Kwords: D0 to D8191 Of these, 7,000 words can be saved to the backup memory (built-in EEP-ROM) using settings in the Auxiliary Area |
||
Operating modes | PROGRAM mode: Program execution is stopped. Preparations can be executed prior to program execution in this mode. MONITOR mode: Programs are executed. Some operations, such as online editing, and changes to present values in I/O memory, are enabled in this mode. RUN mode: Programs are executed. This is the normal operating mode. |
-59%
Omron Sysmac CP1H-XA40DT-D Programmable Controller
$722.70 Original price was: $722.70.$525.60Current price is: $525.60.
Omron Sysmac CP1E-N40DT-D Programmable Controller
$585.65 Original price was: $585.65.$340.25Current price is: $340.25.
Omron Sysmac CP1E-N40DT1-A Programmable Controller
$1,336.37 Original price was: $1,336.37.$545.22Current price is: $545.22.
Author : Admin
- CP1E-N40DT1-A OMRON Sysmac PLC Controllers 16PNP AC PS RS232 24 In
- Cost-effective CP1E with Enhanced Expandability for Analog and Temperature Control
- CP1 Series Micro Programmable Logic Controller CPU Module, application model, normal-type, built-in USB + RS-232C + 1 Option ports, 40 points: 24-inputs/16-PNP (transistor sourcing) outputs, 160 I/O max capacity, 120-240 VAC
- Complete High-speed Counter Functionality.
Category: Electrical Items
Description
Additional information
Weight | 680 g |
---|
Reviews (0)
Be the first to review “Omron Sysmac CP1E-N40DT1-A Programmable Controller” Cancel reply
Shipping & Delivery
Shipping Policy & Terms
We partner with DHL & FedEx for reliable delivery to over 200 countries. Specific options and costs are detailed in your quotation.
Contact Us : [email protected] or
Call/WhatsApp : 90818 00992
Processing and Delivery:
- Stock items ship within 24 hours of payment confirmation. Delivery times and options, including Next Day and Saturday delivery, are specified in your quotation. A tracking number will be provided via email once your order ships.
Express Delivery:
- We offer worldwide express delivery to minimize equipment downtime through our partner warehouses and distribution centers.
Customs Clearance:
- International shipping - items may be subject to customs processing depending on the item's customs value.
Related products
L&T (Larsen & Toubro) MNX 110 Power Contactor 415V AC, 3 Pole
- MNX Contactor 110A 3P 415V AC AC-3 240V AC Coil 50/60 Hz
- MNX power contactor are mainly used in motor feeder ad control system applications.
- The range is availabe from 9A to 650A (AC-3) and provides a relaible performance across diverse condition like high ambient temperature, humidity etc.
- Standardized accessories and spares are available for the entire range
L&T (Larsen & Toubro) MNX 12 Power Contactor 240V AC, 3 Pole
- MNX power contactor are mainly used in motor feeder ad control system applications.
- The range is availabe from 9A to 650A (AC-3) and provides a relaible performance across diverse condition like high ambient temperature, humidity etc.
- Standardized accessories and spares are available for the entire range
L&T (Larsen & Toubro) MNX 185 Contactor 415V AC, 3 Pole
- MNX Contactor 185A 3P 415V AC AC-3 415V AC Coil 50/60 Hz
- MNX power contactor are mainly used in motor feeder ad control system applications.
- The range is availabe from 9A to 650A (AC-3) and provides a relaible performance across diverse condition like high ambient temperature, humidity etc.
- Standardized accessories and spares are available for the entire range
L&T (Larsen & Toubro) MNX 9 Power Contactors 240V AC, 3 Pole
- MNX power contactor are mainly used in motor feeder ad control system applications.
- The range is availabe from 9A to 650A (AC-3) and provides a relaible performance across diverse condition like high ambient temperature, humidity etc.
- Standardized accessories and spares are available for the entire range
L&T (Larsen & Toubro) MNX 95 Power Contactor 415V AC, 3 Pole
- MNX Contactor 95A 3P 415V AC AC-3 110V AC Coil 50/60 Hz
- MNX power contactor are mainly used in motor feeder ad control system applications.
- The range is availabe from 9A to 650A (AC-3) and provides a relaible performance across diverse condition like high ambient temperature, humidity etc.
- Standardized accessories and spares are available for the entire range
Schneider Electric MCB 25A-xC60-415V-3P-C-A9N3P25C
- Schneider Electric A9N3P25C Acti 9 MCB xC60 3P 25A
- Suitable for isolation, guarantees operational safety at the downstream
- Avoids false insertion of cables and loose termination with pull up terminals
- Field fittable auxiliaries available for monitoring and remote tripping
- Increased service life, thanks to fast closing mechanism
- Total flexibility with Line-Load reversibility
Schneider Electric MCB 32A-xC60-415V-3P-C-A9N3P32C
- Schneider Electric A9N3P32C Acti 9 MCB xC60 3P 32A C
- Suitable for isolation, guarantees operational safety at the downstream
- Avoids false insertion of cables and loose termination with pull up terminals
- Field fittable auxiliaries available for monitoring and remote tripping
- Increased service life, thanks to fast closing mechanism
- Total flexibility with Line-Load reversibility
Schneider Electric MCB 40A-xC60-415V-3P-C-A9N3P40C
- Schneider Electric MCB 3P-C-40A-xC60-415V-A9N3P40C
- Suitable for isolation, guarantees operational safety at the downstream
- Avoids false insertion of cables and loose termination with pull up terminals
- Field fittable auxiliaries available for monitoring and remote tripping
- Increased service life, thanks to fast closing mechanism
Reviews